Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Load Analyzer, CT PT Analyzer

Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT AnalyzerSummary:CT PT analyzer is used to measure all kinds of current transformer and voltage transformer. It can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated b

Featured Products

Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT Analyzer

Summary:

CT PT analyzer is used to measure all kinds of current transformer and voltage transformer. It can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one time test. The tester can automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.

 

Applications:

Tests for current transformer:
1) Excitation curve and parameters test
2) Turns ratio test
3) Ratio and phase error test
4) Polarity mark check
5) Winding resistance measurement
6) Secondary loop burden measurement
7) Error line curve test for protection CT
8) Transient CT parameters test
9) CT nameplate guess
10) Saturation hysteresis loop curve measurement
Tests for voltage transformer:
1) Turns ratio test
2) Ratio error and phase angle error test
3) Polarity test
4) Secondary burden test
5) Winding resistance test


Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT Analyzer
Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT Analyzer
 

Features:

1. Make evaluation for test results according to selected standards.
2. Make word report for test result.
3. Make word reports one time for multi-group test records on the PC.
4. Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test.
5. Compare excitation curves with saved excitation curves in the same window.

 

Technical parameter

1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2 Power supply: AC220V±10%,50Hz/60Hz±10%
3 Power output: 0.1~125V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output:300VA
6 Maximum knee voltage measurement; 45kv
7 Current measurement:
Range:0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%FS
8 Voltage measurement:
Range:0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
9 Turns ratio measurement:
Range :1~30000,
1~1000 error<0.05%
1000~2000 error<0.1%
2000~30000 error<0.2%
10 Phase measurement: error:±2min,resolution:0.01min
11 Coil resistance measurement:
Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.1%RDG+0.01%FS
Maximum resolution:0.1mΩ
12 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree
13 CT Secondary burden:
Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution 0.001ohm
14 PT Secondary burden:
Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15 Saved data groups:>1000groups
16 Work condition: Temperature:-10ºC~50ºC, moist:≤90%
17 Size: 485mm×356mm×183mm
18 Weight: <15Kg
Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT Analyzer
 

Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT Analyzer
Automatic Current Transformer and Voltage Transformer Tester, Transformer Excitation Burden Analyzer, CT PT Analyzer
 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours